Make your own power from the sun, and your own cooking gas and fertiliser from the pigs. Step by step, for homes in Aotearoa.

← Learn

New Zealand gets about 4 hours of strong sun a day

That’s an average of about 4 “sun hours” a day (NASA’s long-term average: Auckland 4.3, Wellington 4.2, Christchurch 4.0, Gisborne 4.3). December gives about 6.3 to 6.7, but June only about 1.4 to 2. The winter drop is big, much bigger than in the tropical Pacific. A set of panels that covers your needs in summer will cover only a part of them in winter. Plan for June, not December, and plan a backup.

  • Panels make DC power from the sun.
  • A hybrid inverter (an all-in-one “solar inverter charger”) does three jobs: an MPPT charge controller for the panels, an inverter that makes 230 V AC for the house, and a charger that can use the grid or a generator as backup.
  • Batteries store the day’s power for the night.

“24 V” or “48 V” is the battery voltage. The panels run at a much higher voltage.

📷 What it looks like

A wall-mounted hybrid inverter with a bank of sealed (AGM-type) batteries
A wall-mounted hybrid inverter with a bank of sealed (AGM-type) batteries📷 PowerAfricaSolar · CC BY-SA 4.0
Small portable generators
Small portable generators📷 Maksym Kozlenko · CC BY-SA 4.0
A thatched house with solar panels
A thatched house with solar panels📷 Demeester · CC BY-SA 3.0

Real photos to give you an idea. Your gear may look different. Watch the videos below to see it working.

Two systems: 24 V or 48 V?

24 V system48 V system
Inverter3 kW hybrid, e.g. MUST PV18-3024 VHM or SRNE HF2430S80-H5–6 kW hybrid, e.g. Growatt SPF 5000 ES or SPF 6000 ES Plus
Panels4 × 440 W = 1.76 kW (all 4 in series, one string)8 × 440 W = 3.52 kW (8 in series); up to 12 with a 2-MPPT inverter
Lithium battery25.6 V 200 Ah = 5.1 kWh (about 3.7 kWh to use)51.2 V 200 Ah = 10.2 kWh (about 7.4 kWh to use)
or AGM battery2 × 12 V 200 Ah in series = 4.8 kWh (only 2.4 kWh to use)4 × 12 V 200 Ah in series = 9.6 kWh (only 4.8 kWh to use)
Power a day (average)about 5.7 kWh (2.6 kWh in June, in Auckland)about 11.5 kWh (5.3 kWh in June, in Auckland)
Battery current at full powerabout 150 A: thick 70 mm² cableabout 126 A at 5 kW: 50 mm² cable
Good forSmall house: fridge, lights, fans, TV, phonesFamily house: plus freezer, washing machine, pump, some air-con
Hardware cost (NZ$, before freight)about $4,500–8,000about $8,500–14,000

Our advice: if you can afford it, go 48 V. Same power at half the current means thinner cables, less heat, and room to grow. Specs from the makers’ datasheets (check the exact model and version you buy: they change).

🔍 Choosing solar panels: good, cheap and what to check

TypeWhat it isGood for
Monocrystalline (mono PERC, TOPCon, HJT)Black cells, about 20–23% efficient. TOPCon and HJT are the newer, better kinds.Most homes today: best power for the space
Bifacial (two-sided)Glass on both sides, so the back also catches light bounced off the ground: about 5–20% more power. Costs more.Ground frames or carports over light-coloured ground (white stones, concrete, sand). Not much gain flat on a roof.
PolycrystallineBlue speckled cells, older and about 15–17% efficient.Cheap second-hand panels: fine if there is room for more of them
Flexible / thin-filmLight and bendy, but wear out faster in sun and heat.Boats, caravans, curved roofs. Not for a house system.

What to look for in a decent panel

  • A known brand with a long warranty: 25–30 years on power output and at least 10 years on the panel itself. Ask for the panel’s data sheet and test certificates (IEC 61215 and IEC 61730).
  • Strong frame and glass: 3.2 mm glass and a mechanical load rating of 5,400 Pa or more (important for cyclones in Aotearoa).
  • Made for heat and salt: a low temperature coefficient (around −0.30 %/°C or better) and a salt-mist test (IEC 61701) for houses near the sea.
  • Cheap no-name panels often give less than the label says and fade within a few years. Pay a bit more for the panels you will keep for 25 years.

Buying second-hand? Check every panel

  • No cracked glass, no brown or yellow patches, no “snail trail” lines across the cells, no burn marks.
  • Junction box on the back closed and dry, cables and MC4 plugs not cracked.
  • In full sun, measure Voc with a multimeter: it should be close to the number on the label. Way lower means a bad panel.
  • Buy panels of the same model for one string: mixed panels pull each other down.

📋 Reading the label on the back of a panel

Every panel has a sticker on the back with its numbers. This is an example for a 440 W panel (your panel’s numbers will be a little different):

PHOTOVOLTAIC MODULEModel: XX-440M (example)Maximum Power (Pmax)440 WPower Tolerance0 ~ +5 WMax Power Voltage (Vmp)35.0 VMax Power Current (Imp)12.57 AOpen Circuit Voltage (Voc)42.8 VShort Circuit Current (Isc)13.42 AModule Efficiency21.4 %Temp. Coefficient of Voc−0.26 %/°CMaximum System Voltage1500 V DCMax Series Fuse Rating25 AOperating Temperature−40 ~ +85 °CSTC: 1000 W/m², 25 °C, AM 1.5
On the labelWhat it means
Pmax (watts)The most power the panel makes in perfect test conditions. In real sun expect about 70–85% of it.
Vmp and ImpThe volts and amps while the panel is working at its best. Vmp × Imp = Pmax (35.0 V × 12.57 A ≈ 440 W). Use these to check what the inverter will actually see.
Voc (open circuit voltage)The volts with nothing connected: the highest the panel ever gives. Add up Voc for a series string and keep it under the inverter’s maximum PV voltage (and above its start-up voltage).
Isc (short circuit current)The most amps the panel can push. Your cables, fuses and the inverter’s PV current limit must handle it.
Power tolerance0 ~ +5 W means the panel is never below its rating. A minus number (e.g. ±3%) means it might be.
EfficiencyHow much of the sunlight becomes power. Above 20% is good today.
Temperature coefficientHow the numbers change with heat. Voc goes UP on cold mornings (about 10% more), and power goes down on hot days (about −0.3% for every °C above 25 °C).
Maximum system voltageThe highest string voltage the panel itself can be part of (1000 V or 1500 V). Your inverter limit (often 500 V) is usually lower, so that is the one that counts.
Max series fuse ratingThe biggest fuse allowed for that panel. Matters when 3 or more strings are joined in parallel.
STCThe lab test conditions behind every number: strong sun (1000 W/m²) and a cool 25 °C panel. Real roofs in the islands are hotter, so real output is lower.

⚖️ Mixing different panels: what to expect

Best is the same panel model in a string. If you mix, the weakest panel sets the pace, but which number matters depends on how they are wired:

In series (+ to −)In parallel (+ to +, − to −)
What adds upVoltsAmps
What the weakest panel limitsThe amps (Imp). The same current flows through every panel, so the lowest-amp panel holds the whole string back.The volts (Vmp). All panels share one voltage, so the lowest-volt panel pulls the others down.
Safe to mix ifImp is within about 5–10% (watts and volts can differ)Vmp is within about 5–10% (watts and amps can differ)
  • Example (series): our 440 W panel (Imp 12.6 A) with an old 300 W panel (Imp 9 A). The string runs at about 9 A, so the 440 W panel only gives about 35 V × 9 A ≈ 315 W. You lose about 125 W.
  • Example (parallel): a 440 W panel (Vmp 35 V) next to a small 12 V-style panel (Vmp 18 V) is a bad match: the big panel is dragged down to about 18 V. Two panels with Vmp 35 V and 34 V work fine together even if their watts differ.
  • Got different panels? Put each kind in its own string. If your inverter has 2 MPPT inputs, give each string its own input; otherwise use a second charge controller or inverter.
  • Mixed panels never damage anything if the volts and amps stay inside the limits: you just get less power than the labels add up to.

☀️ How much power will I get?

Uses NASA’s long-term sun numbers for each island group, with 25% taken off for heat, dust, salt and cable losses. Real days vary: a cloudy week gives much less.

Solar array3.52 kW
Average day11.3 kWh
Worst month (winter)5.2 kWh
Best month (summer)17.6 kWh
Battery you can use (after inverter loss)6.9 kWh
Nights it covers2.3

Red bars are months where the sun gives less than your home uses: run the generator or grid backup, or add panels.

What do you run each day?

Your home uses about 5.1 kWh a day. About 3 kWh of that is after dark and comes from the battery. Your panels cover it most of the year, but not in the winter months (May to August).

A rule of thumb: in New Zealand, each 1 kW of panels gives about 3.0 to 3.3 kWh a day on average, 1.1 to 1.5 kWh in June and 4.7 to 5.1 kWh in December.

🔋 Batteries: lithium (LiFePO4) or AGM?

AGM (sealed lead-acid)LiFePO4 (lithium iron phosphate)
How much you can use50% each day (deeper kills it fast)80% each day
How many cyclesabout 600 at 50% (under 2 years of daily use)about 2,500 at 80% (7+ years)
HeatHates heat: at 30 °C life roughly halvesCopes better; the BMS stops charging if too hot or cold
Weight for ~5 kWhabout 120 kg (two 60 kg batteries)about 39 kg
Cost per kWh you can useabout NZ$750about NZ$460–510

AGM is cheaper to buy, but lithium costs less per kWh you can actually use and lasts several times longer, especially in Aotearoa’s heat. Choose a lithium battery with a BMS strong enough for your inverter (200 A for a 3 kW 24 V system, 150 A+ for 5 kW 48 V), and ideally one that talks to the inverter by cable.

Wiring a battery bank

  • Series adds volts: 2 × 12 V 200 Ah = 24 V 200 Ah. 4 × 12 V = 48 V.
  • Parallel adds amp-hours: two 24 V 200 Ah strings = 24 V 400 Ah. Use equal-length cables to busbars.
  • Never mix old and new batteries, or different sizes, in a bank.
  • Never take 12 V from one battery in a 24 V or 48 V bank.
  • Buy lithium as one battery at the right voltage. Don’t join “12 V lithium” batteries in series unless the maker allows it.

Charge settings (examples)

24 V48 V
AGM absorb28.4–29.2 V56.8–58.4 V
AGM float27.0–27.6 V54.0–55.2 V
LiFePO4 charge28.4 V (8S)56.8 V (16S)
LiFePO4 float27.0 V54.0 V
EqualiseOFF (unless the battery maker says otherwise)

Always use YOUR battery’s manual: brands differ. AGM in heat: lower the voltage about 0.5 V (24 V) or 1 V (48 V) at 35 °C.

🔋 Wiring 4 batteries: 24 V or 48 V

The same four 12 V 200 Ah lithium batteries can make a 24 V bank or a 48 V bank. Both store the same power (about 10 kWh). Only the wiring changes.

24 V: 2 in series × 2 in parallel

−+12 V 200 Ah#1−+12 V 200 Ah#2−+12 V 200 Ah#3−+12 V 200 Ah#4+ busbar− busbarfuse 200 A24 V inverter
#1 + to #2 −, and #3 + to #4 −, makes two 24 V pairs. Join the pairs at busbars: 24 V 400 Ah. Tidy, and good for bigger systems.

48 V: all 4 in series

−+12 V 200 Ah#1−+12 V 200 Ah#2−+12 V 200 Ah#3−+12 V 200 Ah#4fuse 175 A48 V inverter
+ of each battery to − of the next. The free − of #1 and + of #4 go to the inverter: 48 V 200 Ah.

24 V without busbars: how we wired ours

Step 1: one bank

24 V inverter+−+−12 V 200 Ah#1+−12 V 200 Ah#2fuse 200 ABank 1 (24 V)+ add another bank here24 V 200 Ah (about 5 kWh)
Two 12 V batteries in series: − of the left battery to + of the right one makes 24 V 200 Ah. The + of the left battery goes to the inverter + (through the fuse), the − of the right battery to the inverter −. That works on its own.

Step 2: add a second bank

24 V inverter+−+−12 V 200 Ah#1+−12 V 200 Ah#2fuse 200 ABank 1 (24 V)+−12 V 200 Ah#3+−12 V 200 Ah#4Bank 2 (24 V)
Each bank is 2 batteries in series: − of the left battery to + of the right one. Join bank 2 to bank 1 left to left and right to right, same terminal each time (+ to +, − to −). Then the + of bank 1’s left battery goes to the inverter + (through the fuse) and the − of bank 1’s right battery to the inverter −. Same result as busbars: 24 V 400 Ah.

💡 Small upgrade: keep the + on bank 1’s left battery but take the inverter − from bank 2’s right battery instead (criss-cross). Both banks then share the work evenly. Use the same thick cable for the jumpers between the banks.

positive (+) negative (−) link between batteries

Your inverter is EITHER a 24 V OR a 48 V inverter, never both. The battery bank must match it exactly. A 48 V bank on a 24 V inverter will destroy it straight away; a 24 V bank on a 48 V inverter won’t even start. Check the label on the inverter (e.g. “PV18-24”, “SPF 5000 ES 48 V”) before you wire anything.

  • Use four of the same battery: same brand, same size, same age.
  • Charge each battery full on its own before you join them, so they start equal.
  • Check the battery manual: many 12 V lithium batteries allow only up to 4 in series (48 V). Some don’t allow series at all.
  • Use the same length and size of cable for each pair, and take the + and − to the inverter from opposite ends (or busbars) so every battery works equally.
  • Fuse and isolator on the main positive cable, close to the batteries. Set the inverter’s battery type and charge voltages for lithium at the right bank voltage.

☀️ Wiring panels: series or parallel

Every panel has two leads with MC4 plugs: − (negative) and + (positive). How you join them decides the volts and amps going to the inverter. Example: 440 W panels, about 33 V and 13 A each when working.

Series: + to −

440 W #1−+440 W #2−+#1 + to #2 −to inverter PV
Volts add, amps stay the same: about 66 V and 13 A. Most hybrid inverters need series, because the panels must give more volts than the battery to charge it.

Parallel: + to +, − to −

440 W #1−+440 W #2−+MC4 Y-branchto inverter PV
Amps add, volts stay the same: about 33 V and 26 A. Join them with MC4 Y-branch plugs. Check the amps are under the inverter’s PV current limit.

Our 4 panels in series, and how to add more

440 W #1−+Voc 43 V43 V440 W #2−+Voc 43 V+ 43 = 86 V440 W #3−+Voc 43 V+ 43 = 129 V440 W #4−+Voc 43 V+ 43 = 172 VTotal Voc ≈ 172 V+ 1 more(optional)to inverter PV#1 − to inverter −#4 + to inverter +
+ of each panel to − of the next panel. The free − on the first panel goes to the inverter −, and the free + on the last panel goes to the inverter +. Each extra panel adds about 43 V: 4 panels ≈ 172 V open circuit. To add one, join the last panel’s + to the new panel’s −, and the new panel’s + becomes the one that goes to the inverter. Stay under the inverter’s 500 V.
  • Our system: all 4 in series (one string): about 43 V Voc per panel, so about 172 V open circuit (up to about 190 V on a cold morning) and about 132 V and 13 A when working. Thin cable is fine at 13 A.
  • The 500 V rule: most hybrid inverters take up to 500 V from the panels (check the label: “Max PV open circuit voltage”). Add up the Voc on every panel in the string, add 10% for cold mornings, and keep it under the limit. With 43 V panels that is about 10 in one string.
  • There is a minimum too: a hybrid inverter only starts charging once the panels reach its start-up voltage (ours needs about 90 V). One 43 V panel can’t start it; 2 in series (86 V) is still short; you need at least 3. Check “PV start-up voltage” and the “MPPT range” on your inverter label, and make sure your string sits inside it.
  • Want more panels than that? Add a second hybrid inverter with its own panels, joined in parallel with the first (see two hybrid inverters below). Both inverters must be made for parallel use.
  • Both together (2S2P): two series pairs, then the pairs in parallel: about 66 V and 26 A. Only use this if your inverter needs lower volts.
  • Only join panels that are the same: same watts, same model. Mixed panels pull each other down.
  • Cover the panels or work at night: panels make live DC voltage whenever light hits them. Use the PV isolator before plugging or unplugging.
  • Always do the voltage check below before you connect a long series string.

☀️ Panels: series, parallel and the voltage check

  • Series (+ of one to − of the next) adds the volts; the amps stay the same as one panel.
  • Parallel (two equal strings joined) adds the amps.
  • Every string on one MPPT must have the same number of the same panels.
  • Face the panels north, tilted about 15–20°. No shade between 9am and 3pm: even one shaded panel pulls a whole string down.
  • Three or more strings in parallel need a fuse on each string.
The one check you must never skip

Total open-circuit voltage of a string must stay under the inverter’s max PV voltage, even on a cool morning:

panels in series × panel Voc × 1.04

Example (440 W panel, Voc 39.4 V): 8 in series = 8 × 39.4 × 1.04 ≈ 327 V, under a 450 V limit ✅. 12 in series ≈ 490 V ❌ too high: it can destroy the inverter. The voltage must also stay inside the MPPT range when the panels are hot (about 20% lower).

🔌 How it all connects

8 × 440 W panels in one string (8S) = 3.52 kW4–6 mm² PV cablePV isolatorDC, lockable4–6 mm² PV cableDC surge SPDHybrid inverter5 kW, 48 VMPPT solar + charger built in50 mm² (1/0 AWG)Fuse 175 AClass T + isolator48 V batteryLiFePO4 51.2 V 200 Ah (10.24 kWh)the gridgrid (optional)Generatorbiogas / diesel / petrolsized to inputChangeover switchsized by sparkyAC INAC OUT4 mm² / 25 ARCD + breakersswitchboardYour houselights, power pointsframes + rails bonded · 6 mm²earth stake · 6 mm² (check)
DC (panels, battery) AC 240 V Earth (green/yellow)
  • For a family house: fridge, freezer, washing machine, pump, TV, fans, even a small inverter air-con in the middle of the day.
  • Battery cable: 50 mm² copper, each lead 2 m or shorter. Thinner than the 24 V system because the current is lower, with less heat and less loss.
  • Fuse at the battery positive: 175 A Class T, then a DC battery isolator. Battery BMS at least 150 A.
  • Panels: 8 × 440 W in one string ≈ 327 V cold, under the Growatt’s 450 V limit and inside its 120–430 V MPPT range. 12 in one string (490 V) would BREAK it: use the 2-MPPT ES Plus with 6 + 6 instead.
  • A 48 V lithium battery that talks to the inverter (CAN/RS485 cable) is the easiest and safest choice: the inverter then charges by the battery’s own rules.

⚡ More power: two hybrid inverters together

Need more than one inverter can give? Some hybrid inverters can be joined in parallel: two 5 kW inverters work as one 10 kW system. They share one battery bank and each one has its own panels.

Panels Aown stringPanels Bown stringSwitchboard→ houseAC OUTInverter Asame modelInverter Bsame modelparallel cablefusefuseOne shared battery banksame voltage as both inverters
  • Only inverters made for it. The manual must say “parallel operation” (e.g. Growatt SPF 5000 ES: up to 6 in parallel, with its parallel kit). Many cheap inverters can’t do it: joining them will blow them up.
  • Same model, same voltage (both 24 V or both 48 V), same firmware and the same settings. Set each one to “parallel” mode in its menu.
  • One shared battery bank. Each inverter gets its own battery cable and fuse, and the cables must be the same length and size.
  • Each inverter has its own panels. Never join the PV inputs of two inverters.
  • The AC outputs are joined exactly as the manual shows (equal-length cables, often with the parallel kit’s cables). A licensed electrician does the 240 V side.
  • Often simpler: buy one bigger inverter (e.g. a 48 V 8–10 kW) instead of two small ones. Parallel is great for adding power later.

🧰 Cable sizes and protection

Cable24 V / 3 kW48 V / 5 kWProtection
Battery ↔ inverter (each lead 2 m max)70 mm² (2/0 AWG), about 152 A50 mm² (1/0 AWG), about 126 AClass T fuse at the battery + (200 A / 175 A), DC battery isolator
Panels → inverter4 mm² or 6 mm² double-insulated, UV-proof PV cable (6 mm² for long runs), matching MC4 plugs of the same brandDC PV isolator (rated for the string voltage), DC surge protector
Inverter AC out → house2.5 mm², 16 A breaker4 mm² / 25 A (or 6 mm² / 32 A)30 mA RCD on house circuits, AC surge protector
Grid → inverter AC inSized for the house load PLUS battery charging: the electrician works it out from the inverter manualIts own breaker / isolator
EarthAbout 6 mm² green/yellow copper for frames, rails and the earth stake (a starting point; the electrician confirms)Common house earth, not a separate “solar earth”

Voltage drop: keep battery cable drop under 1% and DC under 3%. Formula: drop (V) = 2 × length (m) × amps × 0.0175 ÷ cable size (mm²). Example: 152 A over 2 m of 70 mm² loses 0.15 V (0.7%). Good.

  • Crimp lugs with a proper hydraulic or ratchet crimper and the right die. No pliers, no solder-only lugs, no washers between the lug and the terminal.
  • Fuse and isolator as close to the battery as possible.
  • Never unplug MC4 connectors while the panels are working: turn off the PV isolator first. Panels are live whenever the sun shines.

⏚ Earthing: keep the family safe

  • Earth stake: a copper earth rod driven into the ground, joined to the house’s main earth bar. One earth system for everything, not a separate “solar earth”.
  • Bond the panel frames and rails with proper earthing clips that bite through the coating, so a broken panel can never make the frame live.
  • Inverter case connects to the main earth (PE terminal).
  • Neutral–earth (MEN) link: when running off-grid, the inverter output needs a neutral-to-earth bond so RCDs and breakers can trip. Some inverters (e.g. Victron MultiPlus-II) do this automatically with a relay in battery mode and open it when the grid connects. Many cheaper hybrids do NOT. Getting this wrong either way is dangerous: this is a job for the electrician.
  • RCDs (30 mA) on the house circuits, tested in both grid and off-grid mode.
  • Surge protection on the PV (DC) and AC sides, important in lightning season.

🔌 Using the grid as backup

A hybrid inverter can take the grid (or a generator) into its AC IN, charge the battery from it, and pass power through to the house when the sun and battery run low. You choose how in the settings:

SBU (Solar → Battery → Utility)Best for off-grid living: sun first, then battery, and the grid only when the battery gets low. Our pick.
Solar firstSun first; the grid takes over when the sun drops or the battery reaches its limit.
Utility firstGrid powers the house; solar and battery only for blackouts.
Charging priorityA separate setting: solar only, solar first, or solar + grid. Use “solar only” or “solar first” to save money.

Never feed power back into the grid without your lines company’s approval. Never plug the inverter output into a wall socket. Using the grid only as backup input is the simple, safe way.

⛽ A generator as backup: biogas, diesel or petrol

No grid connection, or the grid keeps dropping out? A generator plugs into the same AC IN on the hybrid inverter. On cloudy days and in winter, when the sun can’t keep up, run the generator for a few hours: the inverter charges the battery from it and runs the house at the same time.

FuelGoodNot so good
🐖 BiogasFree fuel from your own pigs or cows. A petrol generator runs on biogas with a mixer kit (start on petrol, then switch over).About 50–75% of the generator’s petrol power. Uses about 0.7–0.9 m³ of gas per kWh, so a 2 m³ a day digester gives roughly 2–3 kWh: enough to top up the battery, not to run the house all day.
🛢️ DieselTough and long-lasting, cheaper to run per kWh than petrol, and good for running every day. A diesel engine can also run “dual fuel”: a little diesel to light it, biogas for the rest.Costs more to buy, heavier and louder. Don’t run it on very light load for hours (it gums up): give it a proper job like charging the battery.
⛽ PetrolCheap to buy and light to move. An “inverter generator” gives clean, steady power that hybrid inverters like.Costs the most to run, shorter engine life. Petrol goes stale after a few months in the tank.

How big?

  • 24 V system (3 kW): a 3–5 kVA generator.
  • 48 V system (5–6 kW): a 5–8 kVA generator.
  • In the inverter settings, turn down the maximum AC charging current so charging plus the house uses no more than about 70% of the generator’s power. Otherwise it will bog down and cut out.

Connecting it safely

  • If you have the grid too, fit a changeover switch (Grid / OFF / Generator) before the inverter’s AC IN, so only one can be connected at a time. This is in the wiring diagram above.
  • Never let a generator feed back into the power lines: it can kill a line worker fixing the power after a storm. A registered electrician fits the changeover switch.
  • Cheap open-frame generators can have shaky power that some hybrid inverters reject. Set the inverter’s AC input to the wide “APL” / generator range, or buy an inverter generator.
  • Many hybrid inverters have a “dry contact” that can start an electric-start generator by itself when the battery runs low. Check your inverter’s manual.
  • Earth the generator frame as its manual says.

Generator fumes kill. Always run it outside, at least 3 m from doors and windows, never in the house, garage or a closed shed. Store fuel away from the house and out of reach of kids. Let it cool before refuelling.

How to run a generator on biogas →

🌀 Cyclones, salt and heat

  • Mount panels for cyclone winds: rails screwed into rafters (not just roofing iron), clamps and screws at the right spacing, extra care at roof edges.
  • Salt air: 316 stainless fixings, aluminium rails, and keep different metals apart so they don’t corrode.
  • After every cyclone: treat loose wiring as live, check clamps and cables before switching back on.
  • Batteries and inverter: shaded, dry, ventilated, above flood level, out of reach of kids. Don’t seal indoor gear in an airtight box outside: it will overheat.

🛒 Where to buy

  • In New Zealand: ask local solar and electrical businesses for a quote, an installer and warranty terms. Check that the installer works with a registered electrician.
  • Online: New Zealand and Australian suppliers sell Growatt, SRNE and similar off-grid inverters and lithium kits. Check the warranty is honoured in New Zealand and the gear meets the local standards.
  • Lithium batteries are dangerous goods to ship: ask for the UN38.3 test certificate and use a freight company that accepts them. Never pack them in luggage.

⚠️ Safety first

  • In New Zealand, the AC wiring, switchboard, earthing and any connection to the grid must be done and signed off by a registered electrician, and your lines company must approve a grid connection. Learn the system, plan it, buy the right parts, and work with your electrician. The wiring rules are AS/NZS 3000.
  • A battery short can melt spanners and start fires, even at 24 V. Take off rings and watches, use insulated tools, cover terminals.
  • Panels are live in daylight, even with everything switched off.
  • Ask your installer for a labelled diagram and the shut-down order, and keep it by the inverter.
  • Swollen, hot or burning-smelling equipment: switch off from a distance, keep everyone away, call the electrician.

🎥 Learn the wiring

24 V 3 kW hybrid inverter solar set-up: full tutorialGlenn Lejano · 24 V system · open on YouTube
How to wire four 12 V batteries in series-parallel for a 24 V inverterCopper Silver & Steel · 24 V AGM bank · open on YouTube
48 V Deye hybrid on-grid / off-grid solar set-up: full tutorialGlenn Lejano · 48 V system · open on YouTube
Complete 48 V off-grid solar power systemDIY Solar Power with Will Prowse · 48 V lithium · open on YouTube
How to wire solar panels: series vs parallelDIY Solar Power with Will Prowse · open on YouTube
How to size a wire for off-grid solar: calculation examplesCleversolarpower · open on YouTube
How to size battery cables for a 5 kW invertersolar circuit 360 · open on YouTube
Grounding for all-in-one solar systems (advanced)DIY Solar Power with Will Prowse · earthing · open on YouTube
Hybrid inverters and earthing: neutral-earth bond in each modeRoland W · earthing · open on YouTube
Making the earth-neutral bond on a Sunsynk hybrid inverterSunsynk · earthing · open on YouTube

Videos belong to their makers on YouTube and only load when you tap them. Overseas videos may use different rules (e.g. US grounding): in New Zealand follow your electrician and the local rules.

Next: free cooking gas from the pigs 🐖

Turn pig and cow manure into cooking gas, hot water and liquid fertiliser for the garden.

Biogas guide →